Pure sine wave output
Wide input voltage range and frequency
Large LCD display and LED display
Full microprocessor control, self-diagnosis, battery automatic testing
Pure on-line static bypass, strong overload and fault protection ability
RS232 and SNMP webmaster providers remote monitoring capabilities
MTBF reaches over 2 billion hours, MTTR reaches 20 minutes
| Technical parameters | ||||||
Model | ZC9001 | ZC9002 | ZC9003 | |||
Output capacity | 1000VA | 2000VA | 3000VA | |||
Input | voltage | 120-300VAC | ||||
frequency | 46-54Hz | |||||
power factor | ≥95% | |||||
Output | voltage stabilization | 220VAC(±2%) | ||||
frequency | 50Hz/60Hz±0.5% battery type | |||||
overload ability | <130% 30s >130% 2ms | |||||
peak factor | 3.1(max) | |||||
power factor | 0.7/0.8 optional | |||||
efficiency | >0.85 | |||||
battery | type | Valve control type lead-acid battery | ||||
long-acting type voltage | 36VDC | 72VDC | 96VDC | |||
standard type | 12V/7AH (2) | 12V/7AH (6) | 12V/7AH (6) | |||
Switch time | bypass to inverter | 0ms | ||||
inverter to bypass | <4ms | |||||
protection | over-temperature | Auto switch to bypass output when over temperature | ||||
short circuit | Cut off inverter and bypass output at the same time | |||||
Display | LCD | Chinese/English UPS statusand operation instruction; Display on input voltage, output voltage, current, frequency, battery voltage and charge/discharge current, failure and alarm. | ||||
LED | UPS operation status | |||||
| Alarm sound | battery low voltage | Buzzing every second | ||||
UPS overload | Continuous sound | |||||
UPS failure | Continuous sound | |||||
Alarm sound | RS232 port (SNMP card and USB optional) | |||||
Working environment | temperature | 0℃-40℃ | ||||
humidity | ≤95% | |||||
noise (within 1M) | <50db | <50db | <50db | |||
Weight | 4.6kg (standard type 13kg) | 6.8kg (standardtype 26kg) | 7.4kg (standard type 28kg) | |||
Dimension | host machine | 282*145*220 | 397*145*220 | 397*145*220 | ||
standard type | 397*145*220 | 419*190*318 | 419*190*318 | |||