6-10kV Ring Main Unit, HXGN- 12

Read More>>


Product Detail

Product Tags

Environmental Conditions

◆ Altitude: lower than 1000 m; ◆ Ambient temperature: up to +40°C, greater than -25°C; ◆ Relative humidity: daily average ≤ 95%, monthly average ≤ 90% (+25°C); ◆ Areas without risks of fire, explosion, pollution, chemical corrosion and severe vibration;

Technical Parameters

ItemUnitParameter
Rated voltageMaximum working voltageKV10/ 12
Rated currentA630
Busbar currentIncoming cableA630
Outgoing cable125
Rated short time withstand currentKA20
Rated peak withstand currentKA50
Rated closed-loop breaking currentKA50
Rated mainly active load-breaking currentA630
Rated cable-charging currentKA20
Power frequency withstand voltage (1 min)KV42
Rated lightening impulse withstand voltageKV75
Mechanical enduranceVacuum load break switchtimes10000
Dimension (W×D×H)mm850×900×2000
Weightkg200 ~ 300kg